Our references Industrial wastewater
Torraspapel Motril | MOTRIL | ESPAGNE

Capacity in IE : 70 000
Activity : Paper mill
Year of construction : 1991

TYPE OF TREATMENT

Water treatment
- Coagulation
- Flocculation
- Settling tank

Sludge treatment
- Belt filter press

TECHNICAL DATA OF PLANT

Capacity of treatmentTreated water discharge standards
Daily volume2 100 m³/d
Pollution load70 000 IE
Biological oxygen demand (BOD5)4 200 kg/j30 mg/l
Chemical oxygendemand (COD)9 500 kg/j125 mg/l
Suspended solids390 kg/j35 mg/l
Total Kjeldahl nitrogen1 340 kg/j

The Inhabitant Equivalent (IE) is a notion used in sanitation to evaluate the size of waste water treatment plants, it corresponds to an estimate of pollution caused by the "inhabitant equivalent" defined thus :
- 60 g/inhabitant/day for DBO5
- 90 g/inhabitant/day for suspended matter
- 15 g/inhabitant/day for total nitrogen
- 4 g/inhabitant/day for total phosphor

Télécharger au format PDF