Banque de France | Vic-le-Comte | 63 | FRANCECapacity in IE : 7 500
Capacity in m³ per day : 143
Activity : Paper mill
Year of construction : 1998
TYPE OF TREATMENT
Water treatment- Coagulation
- Flocculation
- Settling tank
- Biological basin
- Settling tank
Sludge treatment- Gravity belt thickener
- Sludge storage tank
TECHNICAL DATA OF PLANT
| Capacity of treatment | Treated water discharge standards | |
| Daily volume | 143 m³/d | |
| Peak flow | 8 m³/h | |
| Pollution load | 7 500 IE | |
| Biological oxygen demand (BOD5) | 450 kg/j | 55 mg/l |
| Chemical oxygendemand (COD) | 1 220 kg/j | 675 mg/l |
| Suspended solids | 330 kg/j | 35 mg/l |
The Inhabitant Equivalent (IE) is a notion used in sanitation to evaluate the size of waste water treatment plants, it corresponds to an estimate of pollution caused by the "inhabitant equivalent" defined thus :
- 60 g/inhabitant/day for DBO5
- 90 g/inhabitant/day for suspended matter
- 15 g/inhabitant/day for total nitrogen
- 4 g/inhabitant/day for total phosphor