Our references Industrial wastewater
PSA Slovaquie | Tarnava | SLOVAQUIE

Capacity in IE : 14 000
Capacity in m³ per day : 1 785
Activity : Others
Category : Cosmétiques
Year of construction : 2005

TYPE OF TREATMENT

Water treatment
- Screening
- Sand and oil separation
- Buffer tank
- Aaeration basin
- Settling tank

Sludge treatment
- Filter press

TECHNICAL DATA OF PLANT

Capacity of treatmentTreated water discharge standards
Daily volume1 785 m³/d
Peak flow150 m³/h
Pollution load14 000 IE
Biological oxygen demand (BOD5)840 kg/j25 mg/l
Chemical oxygendemand (COD)1 740 kg/j125 mg/l
Suspended solids450 kg/j35 mg/l
Total Kjeldahl nitrogen30 mg/l
Total nitrogen3 mg/l

The Inhabitant Equivalent (IE) is a notion used in sanitation to evaluate the size of waste water treatment plants, it corresponds to an estimate of pollution caused by the "inhabitant equivalent" defined thus :
- 60 g/inhabitant/day for DBO5
- 90 g/inhabitant/day for suspended matter
- 15 g/inhabitant/day for total nitrogen
- 4 g/inhabitant/day for total phosphor

Télécharger au format PDF