Project Rasgas - RAS LAFFAN | QATARCapacity in IE : 3 x 4500
Capacity in m³ per day : 3 x 1440
Year of construction : 2006
Project owner : CTJV
Consultant : Technip
TYPE OF TREATMENT
Water treatmentFor each unit :
- Screening 2 mm
- Buffer tank 600 m³
- Aeration tank 2000 m³ with air diffusers
- 2 blowers 74 kW
- Phosphate removal
- Deaerator
- Floating matters storage tank
- Settling tank Ø 14,50 m
- Sand filter 80 m³/h
- Sludge thickener with picket fence
Sludge treatment
Common equipments for the 3 units :
- Anaerobic sludge digestion
- 2 sludge centrifuge decanters
- Mobile sludge storage skip
- Deodorizing of the waste water lifting station
TECHNICAL DATA OF PLANT
| Capacity of treatment | Treated water discharge standards | |
| Capacity of treatment | 13 500 IE | |
| Daily volume | 4 320 m³/d | |
| Peak flow | 750 m³/h |
| Biological oxygen demand (BOD5) | 1 728 kg/d | 50 mg/l |
| Chemical oxygen demand (COD) | 2 970 kg/d | 150 mg/l |
| Suspended solids | 1 728 kg/d | 50 mg/l |
| Total Kjeldahl nitrogen | 192 kg/d | 75 mg/l |
| Total nitrogen | 192 kg/d | |
| Total phosphorus | 48 kg/d | 9,87 mg/l |
The Inhabitant Equivalent (IE) is a notion used in sanitation to evaluate the size of waste water treatment plants, it corresponds to an estimate of pollution caused by the "inhabitant equivalent" defined thus :
- 60 g/inhabitant/day for DBO5
- 90 g/inhabitant/day for suspended matter
- 15 g/inhabitant/day for total nitrogen
- 4 g/inhabitant/day for total phosphor