Our references Domestic wastewater
Kesckemet | Hungary

Capacity in IE : 250 000
Capacity in m³ per day : 48 000
Year of construction : 1994
Project owner : City of Kesckemet
Consultant : Melyepterv

TYPE OF TREATMENT

Water treatment
- Screnning
- 4 activation tank of 3000 m³ with aeration by air diffusers
- 3 blowers 200 kW
- Dearator
- 4 settling tank Ø 36 m
- Chlorination

Sludge treatment
- 3 digester of 2460 m³ with cogeneration
- 2 belt filter press

TECHNICAL DATA OF PLANT

Capacity of treatmentTreated water discharge standards
Capacity of treatment250 000 IE
Daily volume48 000 m³/d
Peak flow2 667 m³/h
Biological oxygen demand (BOD5)14 400 kg/d25 mg/l
Chemical oxygen demand (COD)32 000 kg/d120 mg/l
Suspended solids12 000 kg/d30 mg/l
Total Kjeldahl nitrogen2 400 kg/d30 mg/l
Total nitrogen2 400 kg/d
Total phosphorus576 kg/d

The Inhabitant Equivalent (IE) is a notion used in sanitation to evaluate the size of waste water treatment plants, it corresponds to an estimate of pollution caused by the "inhabitant equivalent" defined thus :
- 60 g/inhabitant/day for DBO5
- 90 g/inhabitant/day for suspended matter
- 15 g/inhabitant/day for total nitrogen
- 4 g/inhabitant/day for total phosphor